The Fluke 1735 Power Logger is the ideal electrician or technician's tool for
conducting energy studies and basic power quality logging. Set up the Fluke 1735
in seconds, with the included flexible current probes and color display. The
Fluke 1735 logs most electrical power parameters, harmonics and captures voltage events.
Applications
Load studies – verify electrical system capacity before adding loads
Energy assessments – quantify energy consumption before, and after
improvements, to justify energy saving devices
Harmonics measurements –
uncover harmonic issues that can damage or disrupt critical equipment
Voltage
event capture – monitor for dips and swells that cause spurious resets or
nuisance circuit breaker tripping Log the most common parameters
Designed to
measure the most critical three-phase power parameters, the Fluke 1735 can log rms
voltage, rms current, phase angle, voltage events, voltage and cur-rent THD,
voltage and current harmonics up to the 50th, active power, reactive power,
power factor, active energy, reactive energy, and more. With memory for up
to 45 days of data, the Fluke 1735 can uncover intermittent or hard-to-find
issues.
Easy to use
The four current probes are connected with one plug, the instrument
automatically detects, scales and powers the probes. These variable range
current probes are easily set to 15 A, 150 A, or 3000 A for high accuracy in
nearly any application. The voltage connections are single leads, enabling easy
and quick setups. The color screen provides instant confirmation that
connections are correct, and then logging begins when you press the RECORD
button.
|
|
top>> |
|
General |
| Display |
¼ VGA Graphic Color transmissive displays 3 0 x 40 Pixel with additional
background lighting and adjustable contrast, text and graphics in color |
| Quality |
Developed, designed and manufactured
according to DIN ISO 9001 |
| Memory |
4 MB Flash memory, 3.5 MB for logging data |
| Interface |
RS- 3 SUB-D socket; 115. k Baud, 8 data bits, no parity, 1 stop bit,
firmware updates are possible with the RS- 3 interface (9-pole extension
cable) |
| Sample rate |
10. 4 kHz |
| Line frequency |
50 Hz or 60 Hz, user-selectable, with
automatic synchronization |
| Power supply |
NiMH battery-pack, with ac adapter (15
V to 0 V/0.8 A) |
| Operation time with battery |
Typical > 1 hours with backlight low
and > 6 hours with backlight high |
|
V-rms wye Measurement |
| Measuring Range |
57 V/66 V/110 V/1 0 V/1 7 V/ 0 V/ 30 V/ 40 V/ 60 V/ 77 V/347 V/ 380 V/400
V/417 V/480 V ac |
| Intrinsic Error |
± (0. % of measured value. + 5 digits) |
| Operating Error |
± (0.5 % of m. v. + 10 digit) |
| Resolution |
0.1 V |
|
V-rms Delta Measurement |
| Measuring Range |
100 V/115 V/190 V/ 08 V/ 0 V/380 V/ 400 V/415 V/450 V/480 V/600 V/ 660
V/690 V/7 0 V/830 V ac |
| Intrinsic Error |
± (0. % of m. v. + 5 digit) |
| Operating Error |
± (0.5 % of m. v. + 10 digit) |
| Resolution |
0.1 V |
|
A-rms Measurement |
| Flexi Set I Ranges |
15 A/150 A/3000 A rms (at sine) |
| Current clamp ranges |
1 A/10 A |
| Resolution |
0.01 A |
Ranges
(150 A/3000 A and 1 A/10 A) |
Intrinsic error: ± (0.5 % of m. v. + 10
digit) |
| Operating error: ± (1 % of m. v. + 10
digit) |
Ranges
(15A) |
Intrinsic error: ± (0.5 % of m. v. + 0 digit) |
|
Operating error: ± (1 % of m. v. + 0 digit) |
|
|